EX E SYSTEM SOLUTION
JUNCTION BOXES/CABINETLOCAL CONTROL STATION
TECHNICAL SPECIFICATION
Enclosures are suitable for installations in areas where an explosive atmosphere ofgases, steam, and dust may occur (i.e., in Zones 1 and 2 in gas areas and 21 and 22 indust areas). Various sizes of hinged door and screw cover types are certified by ATEXand IECEx. ENSTO is an expert in providing customer-specific Ex enclosing solutions forhazardous areas. Standard enclosures can be delivered with a multitude of optionalsolutions and features, including any dimension, material, surface treatment, RAL color,flanges, and windows. Additionally, we provide special design enclosures developedtogether with customers according to their needs. The maximum size is up to 1000(W) x2000(H) x 800(D) mm.
Material |
SS304/316 |
Surface Treatment | Hairline / Brushed |
Gasket | Special Closed-Cell Gasket |
Degre Of Protection | IP66 |
Impact Resistance |
7Nm |
Operating Temperature | -55...85oC |
Ex Empty Certificates |
Presafe 14 ATEX 5378U, IECEx PRE 14.0042U. |
Standard Marking Junction Boxes | || 2G Ex e ||C Gb |
Standard Marking Control Station | || 2G Ex de IIC T6 Gb |